کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
248836 502585 2011 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Numerical modelling of industrial indoor environments: A comparison between different turbulence models and supply systems supported by field measurements
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Numerical modelling of industrial indoor environments: A comparison between different turbulence models and supply systems supported by field measurements
چکیده انگلیسی

Ventilation, heating and cooling systems in industrial premises are important issues as they are related to both energy cost and indoor climate management and the health of the premises’ occupants. The present paper has two aims: (1) to evaluate the performance of Computational Fluid Dynamics (CFD) for planning new or renovating existing industrial ventilation systems, and (2) to evaluate the performance of two different supply principles in a contaminant-intensive process with temperature and density stratification.The comparisons between measurements and simulations show good agreement, with an average deviation of 1.1 °C for temperature and 0.11 m/s for velocity when using the most accurate model. Of the compared two-equation models (RNG, SKE and RKE), the RNG model produced the results most in agreement with the measurements. Good agreement was also found when measured and predicted values for contaminant removal efficiency were compared.When the mixing and displacement ventilation systems at the facility were compared, an increase in contaminant removal efficiency by a factor of 6 was found during winter for the displacement system, and the performance in terms of heat removal effectiveness increased by a factor of 3 for the same case. One drawback, however, was the slightly higher predicted discomfort and risk of draughts in the winter cases. In the summer cases, the difference in performance between the two systems was smaller. The overall performance of the displacement system decreased due to the diminishing stack effect as the temperature difference between supply air and the air in the room decreased.


► The paper evaluate the performance of CFD for large industrial facilities.
► RNG model resulted in best agreement with the measurements of temperature and flow field.
► Displacement ventilation increase contaminant removal efficiency compared to mixing ventilation.
► Displacement ventilation increase heat removal efficiency compared to mixing ventilation.
► Small increase in risk of discomfort for the displacement system compared to the mixing.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Building and Environment - Volume 46, Issue 11, November 2011, Pages 2365–2374
نویسندگان
, ,