Influence of fire ignition locations on the actuation of smoke detectors and wet-type sprinklers in a furnished office
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Influence of fire ignition locations on the actuation of smoke detectors and wet-type sprinklers in a furnished office
چکیده انگلیسی

Experiments were conducted in a full-scale model office equipped with movable and fixed fire loads to explore the influence of ignition source (movable fire load(s)) conditions on smoke detector and sprinkler actuation. The interior plan dimension is 5.7 m × 4.7 m and the net ceiling height is 3.3 m. Both northeast and southeast wings have a 2.1 m × 0.9 m single door to be opened. Seven fire scenarios (seven different ignited fire load configurations) under natural ventilation were investigated experimentally. The results show that the amount of fire load at the initial stage in a room fire does not markedly affect smoke generation and does not significantly impact the actuation time of the smoke detectors. When the fire source is located near a corner, the plume corner effect greatly increases; smoke detectors and sprinklers can activate quickly and effectively actuate the fire suppression. When the fire source is located in the room's center, given the uncertainty regarding smoke detector and sprinkler actuation, it may not be possible to control the fire spread.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Building and Environment - Volume 45, Issue 6, June 2010, Pages 1448–1457