کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
249428 502609 2007 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
A new formula for determining a minimum recommended value of inlet air velocity from UFAD system to prevent occupants from draught risk
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
A new formula for determining a minimum recommended value of inlet air velocity from UFAD system to prevent occupants from draught risk
چکیده انگلیسی

During the winter period the natural convection flow along a cold window surface can be the cause of thermal discomfort. Warm air blown into the room near the window prevents occupants from draught risk. The paper presents a new formula for determining a minimum recommended value of inlet air velocity. A balance of a momentum flux of flow of the down draught currents and the warm air jet inflow from the UFAD (under floor air distribution) system was a base for the analytical solution. In order to estimate air movement in a typical room, numerical simulations are executed. A computational model of the room with the UFAD system is constructed within the CFD environment developed by Fluent Inc. Ten cases with varying inlet air parameters and a window UU-value are considered. The analytical estimation of minimum inlet air velocity is confirmed by simulation results of temperature and velocity distributions.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Building and Environment - Volume 42, Issue 1, January 2007, Pages 171–179
نویسندگان
,