Hygrothermal performance evaluation of traditional brick masonry in historic buildings
ترجمه فارسی عنوان
ارزیابی عملکرد هیدروترمال سنگ ساختمانی آجری سنتی در ساختمان های تاریخی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
چکیده انگلیسی


• Indirect hygrothermal assessment of traditional masonry.
• Iterative IRT and heat flow metering for walls thermal properties analysis.
• Residual moisture localization and quasi in contact environmental monitoring.
• Moisture influence on thermal performance of brick masonry in heritage buildings.
• Triplication of thermal transmittance value due to lack of masonry natural drying.

Existing buildings account for 40% of total green gas emission in the atmosphere [1] and [2]. Historic and heritage buildings are part of this building stock, and the need for improving their energy performance, despite the derogations for officially protected ones, is supported for achieving the European 2020 Energy Strategy aims [3].However, when dealing with these buildings, not only are the intervention measures constrained by possible architectural preservation requirements, but also the preparatory building diagnosis itself: only non-destructive and non-invasive monitoring techniques are, reasonably, allowed. Therefore, during onsite energy auditing, ad-hoc monitoring protocols should be adopted.In this study, an indirect non-invasive envelope monitoring, for evaluating brick masonry hygrothermal behavior, has been proposed and applied in a heritage building in Antwerp (Belgium). The suggested method is aimed at onsite evaluating the thermal performance of buildings traditional masonry and at quantifying the extent of its alteration due to the moisture distribution variation.Areas detected as wet during iterative passive infrared thermography and environmental monitoring, showed thermal transmittance values more than three times higher than the dry ones on the same masonry surface.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 105, 15 October 2015, Pages 393–411
نویسندگان
, , , ,