Development and experimental validation of a high-temperature heat pump for heat recovery and building heating
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Development and experimental validation of a high-temperature heat pump for heat recovery and building heating
چکیده انگلیسی

The performance of a high-temperature heat pump unit using geothermal water for heat recovery in buildings is experimentally evaluated. The unit consists of a twin-screw refrigeration compressor, a condenser, an evaporator and an oil cooling system. The effect of the cooled oil temperature on the performance of the heat pump unit is experimentally investigated. Results show that the unit stably produces outlet hot water at a constant temperature of 85 °C and performs well in a wide range of high-temperature conditions with a high energy efficiency ratio. The results also indicate that the key to improving the performance of a high-temperature heat pump unit often depend on the selection of proper cooled oil temperature. The optimum cooled oil temperature is 50–65 °C when the condensing temperature is above 70 °C. At these temperatures, the oil cooling system can increase the energy efficiency ratio of the heat pump by 6.3%.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 41, Issue 7, July 2009, Pages 732–737