Enhancing load calculation tools into building simulation programs requires an in-depth revision and fine tuning of the load calculation assumptions prior to the addition of the HVAC system modelling routines. It is of special interest the analysis of transient heat conduction through multi-layer walls where, in order to improve the coupling between the passive elements of the building and the HVAC systems, an improvement of the time resolution in the calculation becomes critical. Several methods have been historically used, although recently Laplace's method has been displaced by the State Space method.This paper proposes a new strategy for fine time resolution on the calculation of the response factors through Laplace's method considering a comparison with the performance of the State Space method when used to calculate conduction transfer functions. Our analysis shows that in order to achieve similar accuracy with both approaches, the State Space method requires significant additional computational time.
Journal: Energy and Buildings - Volume 42, Issue 4, April 2010, Pages 541–546