کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
264993 | 504126 | 2010 | 8 صفحه PDF | دانلود رایگان |
A novel dew point evaporative cooling system for sensible cooling of the ventilation air for air conditioning application was constructed and experiments were carried out to investigate the outlet air conditions and the system effectiveness at different inlet air conditions (temperature, humidity and velocity) covering dry, temperate and humid climates. The results showed that wet bulb effectiveness ranged between 92 and 114% and the dew point effectiveness between 58 and 84%. A continuous operation of the system during a typical day of summer season in a hot and humid climate showed that wet bulb and dew point effectiveness were almost constant at about 102 and 76%, respectively. The experiment results were compared with some recent studies in literature.
Journal: Energy and Buildings - Volume 42, Issue 5, May 2010, Pages 637–644