Energy performance of a cooling plant system using the inverter chiller for industrial building
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Energy performance of a cooling plant system using the inverter chiller for industrial building
چکیده انگلیسی

The purpose of this paper is to clarify energy performance of the cooling plant system in the industrial building using actual measured operating data and numerical simulation analysis. One aspect of industrial buildings is that they have large energy consumption for manufacturing and air-conditioning compared with office and commercial buildings. Some examples of high-efficiency technologies installed in this particular cooling plant system are inverter chillers, integrated cooling towers and a free-cooling system. The inverter chiller which has been put on the market recently is state-of-the-art technology. The maximum COP of the inverter chiller reaches about 18 under certain conditions and integrated cooling towers make lower temperature cooling water as the whole capacity is large. Actual operating data indicates satisfied values for chiller and system COP during the running period and the simulation results show that the cooling plant system can cut down annual electric power consumption by about 48% compared with conventional cooling system.