کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
265569 504173 2006 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Air leakage measurement and analysis in duct systems
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Air leakage measurement and analysis in duct systems
چکیده انگلیسی

Air ducts and related equipments are used in a large number of buildings having thermal comfort. In this study, energy loss related with air leakage is studied. The leakage measurement setup was produced according to NEN-EN standards and the evaluation of data have been conducted by using power law model. The measurements were made on 300 and 1000 mm diameter single circular ducts, 300 mm × 250 mm and 1000 mm × 500 mm flanged joint rectangular ducts, 300 and 630 mm diameter circular beaded slip joint ducts, 300 mm × 200 mm and 500 mm × 300 mm rectangular flanged and drive slip joint ducts, and an branched air distribution system having different diameters for positive internal pressures. Test results have showed that the most of air leakage is from the joints. The seam contribution to air leakage is relatively lower than the joints. Using sealing gaskets help to improve the air leakage by about 50%.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 38, Issue 3, March 2006, Pages 207–213