Impact of ASHRAE's museum climate classes on energy consumption and indoor climate fluctuations: Full-scale measurements in museum Hermitage Amsterdam
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Impact of ASHRAE's museum climate classes on energy consumption and indoor climate fluctuations: Full-scale measurements in museum Hermitage Amsterdam
چکیده انگلیسی


- The energy consumption and the indoor climate were monitored for one year.
- A reference class (ultra-stable), ASHRAE's class AA and A were tested repeatedly.
- Class AA saved 49%, Class A saved 63% of energy compared to the reference class.
- Classes AA and A show decreased hourly and increased daily fluctuations of T and RH.
- It appears that the overall collection degradation risk has not changed significantly.

In the 20th century, museum indoor climates have been conditioned ever more strictly, sometimes beyond guidelines, allowing no fluctuations at all. Among other effects, this has led to excessive energy demands. At the start of the 21st century, interest has increased to condition the indoor climate more reasonable. This study assessed the energy impact of three levels of museum climate control: Reference (21 °C/50% RH, no permissible fluctuations), ASHRAE's Class AA, ASHRAE's Class A. Full-scale measurements were conducted in the museum Hermitage Amsterdam for one year. The results show that Class AA saved 49% and Class A saved 63% compared to the Reference setpoint strategy. Moreover, relaxing the climate specifications decreased hourly fluctuations, but increased daily fluctuations. It is highly likely that the overall degradation risk has not significantly changed for most artefacts.

363

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 130, 15 October 2016, Pages 286-294