Research articleMulti-loop control of UPS inverter with a plug-in odd-harmonic repetitive controller
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی کنترل و سیستم های مهندسی
پیش نمایش صفحه اول مقاله
Research articleMulti-loop control of UPS inverter with a plug-in odd-harmonic repetitive controller
چکیده انگلیسی


- Multi-loop control for the single-phase UPS inverter is proposed.
- A plug-in odd-harmonic repetitive controller regulates the output voltage.
- A simple proportional controller regulates the filter capacitor current.
- The instantaneous value of the reference voltage is feedforwarded.
- The performance is confirmed through simulations and experiments.

This paper proposes an improved multi-loop control scheme for the single-phase uninterruptible power supply (UPS) inverter by using a plug-in odd-harmonic repetitive controller to regulate the output voltage. In the suggested control method, the output voltage and the filter capacitor current are used as the outer and inner loop feedback signals, respectively and the instantaneous value of the reference voltage feedforwarded to the output of the controller. Instead of conventional linear (proportional-integral/-resonant) and conventional repetitive controllers, a plug-in odd-harmonic repetitive controller is employed in the outer loop to regulate the output voltage, which occupies less memory space and offers faster tracking performance compared to the conventional one. Also, a simple proportional controller is used in the inner loop for active damping of possible resonances and improving the transient performance. The feedforward of the converter reference voltage enhances the robust performance of the system and simplifies the system modelling and the controller design. A step-by-step design procedure is presented for the proposed controller, which guarantees stability of the system under worst-case scenarios. Simulation and experimental results validate the excellent steady-state and transient performance of the proposed control scheme and provide the exact comparison of the proposed method with the conventional multi-loop control method.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: ISA Transactions - Volume 67, March 2017, Pages 496-506