کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
5011205 1462475 2017 5 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Analysis on the cooling water system operation under the first time test of 40 Tesla hybrid magnet
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Analysis on the cooling water system operation under the first time test of 40 Tesla hybrid magnet
چکیده انگلیسی

The hybrid magnet of the High Magnetic Field Laboratory has reached its premier goal of 40 T. A detailed analysis has been carried on the cooling water system for insert resistive magnet, and about the de-ionized water quality, the time for purification and the operation parameters. Some phenomena and problems during the resistive magnet excitation have been analyzed. The de-ionized water resistivity presents a continuous declination trend. The flow rate of the de-ionized water and the heat load in both sides of the heat exchanger is imbalance. Some possible reasons were given. The further improvement methods and measures to some problems of the system have been proposed.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Case Studies in Thermal Engineering - Volume 10, September 2017, Pages 95-99
نویسندگان
, ,