چکیده انگلیسی
A numerical model of a novel outside evaporative cooling liquid desiccant dehumidifier (OECD) was developed and the effects of inlet parameters, including the inlet temperature and relative humidity of dehumidified air and evaporative cooling (EC) air, as well as the inlet mass flow rate of solution and so on, on the device performances were investigated in this paper. The results show that as the inlet temperature of solution increased from 31 to 42 °C, the moisture removal rates of OECD were increased by 14.0-18.0% and 31.1-101.5% compared to the non-evaporative cooling dehumidifier (NECD) and the adiabatic dehumidifier respectively, whereas the dehumidification rate was only decreased by about 1.6% with increase in the inlet temperature of LiCl solution from 24 to 44 °C. All these results can provide guidance for the structural design and performance analysis of the dehumidifier in the future.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 82, October 2017, Pages 212-226
نویسندگان
, , , , ,