کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
5017037 1466384 2017 39 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental evaluation of a triple-state sorption chiller
ترجمه فارسی عنوان
ارزیابی تجربی از چیلر جذب سه حالته
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
چکیده انگلیسی
This paper presents the experimental testing results of a novel triple-state sorption chiller with integrated cold storage. The performance of the chiller was measured for hot water inlet temperatures between 65 °C and 95 °C, heat rejection inlet temperatures between 15 °C and 35 °C, and chilled water inlet temperatures between 10 °C and 25 °C. An empirical model was developed for implementation in the TRaNsient SYstem Simulation (TRNSYS) software. To validate the model, a five-hour experimental charge test was conducted during which the hot water and heat rejection inlet temperatures were continuously varied. The model was able to predict the total heat input and heat rejection energy to within 0.7% and 1.3% of the experimentally measured values, respectively.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 81, September 2017, Pages 12-25