کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
5017326 | 1466391 | 2017 | 13 صفحه PDF | دانلود رایگان |
![عکس صفحه اول مقاله: Limits of one-dimensional solutions for orthotropic annular fins under dehumidifying operating conditionsLimites des solutions uni-dimensionnelles pour des ailettes annulaires orthotropes fonctionnant dans des conditions de déshumidification Limits of one-dimensional solutions for orthotropic annular fins under dehumidifying operating conditionsLimites des solutions uni-dimensionnelles pour des ailettes annulaires orthotropes fonctionnant dans des conditions de déshumidification](/preview/png/5017326.png)
- Dry fin parameter (mL) completely governs the fin efficiency for one-dimensional temperature distribution.
- For krzâ¤1, the one-dimensional solution is valid for all considered aspect ratios.
- For 10â¤krzâ¤100, the one-dimensional solution is valid for αââ¥â60.
- For the set of operating conditions, thermal conductivity ratio has a negligible effect on optimum fin dimensions.
Thermal performance characteristics of orthotropic material annular fins subjected to dehumidifying operating conditions are studied using two-dimensional finite element method. The method accounts for non-linear temperature-humidity ratio psychrometric relationship under both partially and fully wet operating conditions. Limits of one-dimensional solutions for orthotropic material fins subject to dehumidifying conditions are investigated in somewhat more detail by introducing dimensionless parameters. The dry fin parameter that fully governs fin efficiency under a set of operating conditions is also defined. The optimum fin dimensions are also estimated for a set of operating conditions and fixed fin volume.
Journal: International Journal of Refrigeration - Volume 74, February 2017, Pages 412-424