کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
653392 1457507 2013 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Investigation of water droplet carryover phenomena in industrial evaporative air-conditioning systems
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Investigation of water droplet carryover phenomena in industrial evaporative air-conditioning systems
چکیده انگلیسی
Water droplet carryover phenomena and pressure drop characteristics in drip-type direct evaporative coolers have been experimentally investigated. Ten different evaporative cooling pads were tested for different air frontal velocities, and the onset of carryover has been determined. The onset of water carryover has been found to be at air velocities between 3.5 and 4.2 m/s. Also, the effect of flute height and pad thickness on pressure drop characteristics of cooling pads has been examined. In addition, it has been determined that for the steady-state operation of drip-type direct evaporative coolers, water temperature in the reservoir approaches the wet bulb temperature and can be taken as constant for long term steady-state operations in practice.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Communications in Heat and Mass Transfer - Volume 47, October 2013, Pages 92-97
نویسندگان
,