In this paper, flow patterns and their transitions for refrigerant R-134a condensing in a microfin tube are visually observed and analyzed. The microfin tube has been provided with different tube inclination angles of the direction of fluid flow from horizontal, α. The experiments were performed for seven different tube inclinations, α, in a range of − 90° to + 90° and refrigerant mass velocities in a range of 53 to 212 kg/m2s for each tube inclination angle during condensation of R-134a vapor. From analysis of acquired data, it was found that the tube inclination strongly influenced the vapor and condensate liquid distribution. Annular flow was the dominant flow pattern for vertical downward flow, α = − 90°. Annular flow, semi annular flow and stratified flow were observed for α = − 60°and − 30°. Annular flow, wavy-annular flow and stratified-wavy flow exist in sequence for horizontal tube. Annular flow and wavy-annular flow were observed for α = + 30°and + 60°. Annular flow, annular-wavy flow, churn flow and slug flow occurred for α = + 90°.