کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
6680665 1428074 2018 14 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental and numerical analysis of a SOFC-CHP system with adsorption and hybrid chillers for telecommunication applications
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Experimental and numerical analysis of a SOFC-CHP system with adsorption and hybrid chillers for telecommunication applications
چکیده انگلیسی
This paper reports about the combined experimental and numerical investigation of a novel small size multi-generation system, for electric (i.e. <10 kW) and cooling (i.e. <20 kW) energy provision to Base Transceiver Stations and small data centers. The proposed concept is based on a high-efficiency natural gas driven SOFC-CHP coupled to commercially available thermally driven adsorption chillers. The main components of the system were experimentally characterized under relevant boundaries and the obtained performance maps were used to implement a TRNSYS model of the whole multi-generation system. The developed model was used to investigate the effect of the sizing of each component as well as the integration of two different commercial thermally driven chillers on the achievable global efficiency. This analysis demonstrated the possibility of getting global energy efficiency up to 0.63 and yearly primary energy savings up to 110 MWh. CO2 emissions avoided are up to 43 t/y.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 216, 15 April 2018, Pages 620-633