کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
6696995 1428352 2018 12 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental and numerical study of airflow distribution optimisation in high-density data centre with flexible baffles
ترجمه فارسی عنوان
بررسی تجربی و عددی بهینه سازی توزیع جریان هوا در مرکز داده با تراکم بالا با بافل انعطاف پذیر
کلمات کلیدی
مراکز داده، مدیریت جریان هوا، تراکم بالا، نقاط رک سوپاپ های انعطاف پذیر،
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
چکیده انگلیسی
In this paper, an innovative airflow optimisation method applying flexible baffles (FBs) set in an air inlet of racks is proposed to improve the airflow distribution in a data centre during the later maintenance and optimisation phase for existing data centres. Two models (i.e. without FBs and with FBs) are developed and compared by numerical simulations in Airpak 3.0 packages. An on-site experiment is conducted to validate these two models. Both the simulation and experimental results show that the use of FBs can effectively improve the thermal environment in the data centre. To optimise the effectiveness of FBs, a series of scenarios (i.e. FBs with different sizes and angles) is analysed and compared, based on which an optimisation method of the data centre with FBs is developed. The optimum thermal environment appears when 20-cm FBs with a 75° angle in the vertical direction of the rack are applied. The temperature drop of the hotspot in the racks reaches about 1.5 °C, which can effectively weaken the rack hotspots. In addition, the results demonstrate that the temperature drop at a certain point on the rack is related to the corresponding point temperature and the size of the FBs. The higher the temperature of the point, or the wider the width of the baffle, the greater the temperature drop.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Building and Environment - Volume 140, August 2018, Pages 128-139
نویسندگان
, , , , ,