Impact of demand controlled ventilation on system performance and energy use
ترجمه فارسی عنوان
تأثیر کنترل تهویه مطبوع بر عملکرد سیستم و استفاده از انرژی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
چکیده انگلیسی
This paper assesses the impact of fan control on both fan energy use and ventilation performance in DCV system of a densely occupied office. Results of a simulation model and realistic measurement setup are compared. The PR control, using air flow rate and VAV-valve position measurements as feedback, causes significantly reduction on fan energy use. These reductions compared to conventional DCV and CAV respectively, are approximately 10% and 72% in case of high occupancy and 50% and 93% in case of low occupancy. Largely, DCV with PR control is strongly considered, especially when occupancy is often expected to deviate significantly from the nominal conditions. Moreover, both simulations and measurements show that there is a clear trade-off between air flow rate deficit and fan energy use, when the fan energy use is lower, the air flow rate deficit is higher and vice versa. Furthermore, the results show that VAV-valve accuracy, characteristics and its lower operational limit hamper the ventilation system in achieving the predicted performance as in the simulation.