Using multiobjective optimizations to discover dynamic building ventilation strategies that can improve indoor air quality and reduce energy use
ترجمه فارسی عنوان
با استفاده از بهینه سازی چند منظوره برای کشف راهکارهای تهیه ساختمان پویا که می تواند کیفیت هوای داخل خانه را بهبود بخشد و مصرف انرژی را کاهش دهد
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
چکیده انگلیسی
Ventilation plays a crucial role in promoting the comfort and health of building occupants. It is sometimes costly in terms of energy consumption, but can also be beneficial from an energy perspective when free cooling is available. This work is an exploratory analysis of the hypothesis that simultaneously optimizing energy and indoor air quality (IAQ) objectives can yield better results than existing ventilation control methods. A multiobjective optimization framework was set up to determine optimal time-resolved outdoor airflow and zone temperature setpoints. Test cases were implemented in a modeled office building by numerical, simulation-based optimization for a core and perimeter zone and for typical weather days in January, July, and October in Philadelphia. Results showed that conventional approaches were dominated by the optimized strategies in some cases. Most strikingly, in the core zone in January, mechanical system energy use was reduced by 20-30% with nearly unchanged or improved IAQ. The optimized strategies employed a low-temperature morning flush, a time-shift of some ventilation to the mid afternoon when outdoor air did not require as much heating, and a reduction in ventilation in the evening when it was not as effective at reducing exposure. Cases in July and October demonstrated another benefit: significant IAQ improvements at low energy cost. The results show that there is significant room for improvement in reducing the energy use associated with providing good IAQ.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 75, June 2014, Pages 272-280
نویسندگان
, ,