کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
7175440 1466380 2018 42 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental assessment of a split air conditioner working with R-417A under different indoor and outdoor conditions
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Experimental assessment of a split air conditioner working with R-417A under different indoor and outdoor conditions
چکیده انگلیسی
The present paper aims to evaluate the performance characteristics of a split air conditioner working with R-417A under different indoor and outdoor operating conditions. A test facility was constructed and experiments were carried out to achieve the research objectives. The indoor conditions were varied in a wide range of air temperature (21-31.4 °C), air relative humidity (40.3%-61.9%) and air velocity (2.8-4.7 m s−1) while the outdoor conditions were changed in range of air temperature (35-51.2 °C) and air relative humidity (40.8%-81.2%). Experimental results showed that the increase in the indoor air temperature causes an enhancement in the system coefficient of performance by about 59.7%, while increasing the outdoor air temperature decreases the system coefficient of performance by about 51.6%. The system cooling capacity using R-417A was lower than that of R-22 by about 33.2% at indoor air temperature of 24.5 °C.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 85, January 2018, Pages 268-281
نویسندگان
, , ,