کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
787451 1466470 2008 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Comparative experimental drift study between a dry and adiabatic fluid cooler and a cooling tower
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Comparative experimental drift study between a dry and adiabatic fluid cooler and a cooling tower
چکیده انگلیسی

Water drift emitted from cooling towers is objectionable for several reasons, mainly due to human health reasons. These objections make the installation of the cooling towers difficult and penalize the COP of the cooling plants. The dry and adiabatic fluid cooler works as a standard fluid dry cooler enhancing the dry cooler's capacity with adiabatic pre-cooling of the air intake. The objectives of this work were twofold: the first one was to review the available drift test methods usually used on cooling towers, and the second one was to carry out drift measurements on a dry and adiabatic fluid cooler and on a cooling tower of similar capacity working in real facilities. No drift was registered on the dry and adiabatic fluid cooler when using the sensitive paper drift test method, while a drift of 0.0023% was measured in the cooling tower.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 31, Issue 7, November 2008, Pages 1169–1175
نویسندگان
, , ,