کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
787571 1466480 2007 14 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Modelling of reciprocating and scroll compressors
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Modelling of reciprocating and scroll compressors
چکیده انگلیسی

This paper presents simple and thermodynamically realistic models of two types of compressors widely used in domestic heat pumps (reciprocating and scroll compressors). These models calculate the mass flow rate of refrigerant and the power consumption from the knowledge of operating conditions and parameters. Some of these parameters may be found in the technical datasheets of compressors whereas others are determined in such a way that the calculated mass flow rate and electrical power match those given in these datasheets.The two models have been tested on five reciprocating compressors and five scroll compressors. This study has been limited to compressors with a maximum electrical power of 10 kW and for the following operating conditions: evaporating temperatures ranging from −20 to 15 °C and condensing temperatures ranging from 15 to 60 °C.The average discrepancies on mass flow rate and power for reciprocating compressors are 1.10 and 1.69% (for different refrigerants: R134a, R404A, R22, R12 and R407C). For scroll compressors, the average discrepancies on mass flow rate and power are 2.42 and 1.04% (for different refrigerants: R134a, R404A, R407C and R22).

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 30, Issue 5, August 2007, Pages 873–886