Partialization losses of ON/OFF operation of water-to-water refrigeration/heat-pump units
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Partialization losses of ON/OFF operation of water-to-water refrigeration/heat-pump units
چکیده انگلیسی


• The dynamic performance of a water to water HP is almost quasi steady.
• Start-up losses are negligible in water to water systems.
• New formula proposed for the PLF evaluation.
• Stand-by losses produce high PLF deterioration at low loads.

This paper presents the results of an experimental campaign for the characterization of the dynamic behavior of a water-to-water refrigeration/heat-pump unit under ON/OFF operation. The unit was previously tested at different water inlet temperatures under steady state conditions, and a very good agreement was found between the instantaneous dynamic performance of the heat pump and the corresponding quasi-steady state operation. In parallel, a series of tests were carried out to quantify the coefficient of performance (COP) degradation as a function of the load ratio, and a simple formula for the Part Load Factor is presented. Results lead to the conclusion that the only non-negligible factor in the COP degradation is the stand-by electrical consumption during the OFF period, especially at low load ratios. Finally, it is concluded that the minimization of the stand-by consumption is a key point for the future improvement of the seasonal performance of water-to-water systems.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 36, Issue 8, December 2013, Pages 2251–2261
نویسندگان
, , , ,