کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
789235 1466396 2016 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental study on the CO2 flow characteristics through electronic expansion valves in heat pump
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Experimental study on the CO2 flow characteristics through electronic expansion valves in heat pump
چکیده انگلیسی


• Flow characteristics of CO2 EEV was investigated in a large operation range.
• The important role of density was identified in the prediction of CO2 flow.
• Dramatic change of flow characteristics was observed above the critical point.

In this study, the influence of key parameters on the EEV mass flow rate was investigated experimentally, including the inlet temperature, inlet pressure and EEV opening. The parametric tests show that a relatively linear variation of CO2 flow could be maintained with the decrease of inlet temperature at higher pressure and the increase of inlet pressure at lower temperature. However, due to the large density changes above the critical point, significant changes in the CO2 flow characteristics were observed with the variations of inlet temperature at lower inlet pressure and the variations of inlet pressure at higher inlet temperature. The important role of CO2 density can be further confirmed by an empirical correlation which incorporates the effects of density, pressure difference and EEV opening, and the maximum deviation of mass flow predictions is below 15.3%.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 69, September 2016, Pages 106–113
نویسندگان
, , , , ,