کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
789630 1466449 2011 18 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Performance analysis of desiccant dehumidification systems driven by low-grade heat source
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Performance analysis of desiccant dehumidification systems driven by low-grade heat source
چکیده انگلیسی

If a desiccant dehumidification system can be driven by a heat source whose temperature is below 50 °C, exhaust heat from devices such as fuel cells or air conditioners can be used as its heat source, thereby saving energy. Therefore, in this study, we used a previously validated simulation model to determine the minimum heat source temperature for driving a desiccant dehumidification system. We considered four desiccant dehumidification systems that can be driven by waste heat—conventional desiccant-type systems (wheel type and batch type with only desiccant), a system with a precooler, double-stage-type systems (a type with two desiccant wheels and a four-partition desiccant wheel type), and a batch-type system with an internal heat exchanger. We found that among these systems, the last system can be driven by the lowest heated air temperature—approximately 33 °C—which is considerably lower than that of the conventional system.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 34, Issue 4, June 2011, Pages 928–945
نویسندگان
, , , ,