کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
789800 | 1466460 | 2010 | 9 صفحه PDF | دانلود رایگان |
![عکس صفحه اول مقاله: Performance analysis of a no-frost hybrid air conditioning system with integrated liquid desiccant dehumidification Performance analysis of a no-frost hybrid air conditioning system with integrated liquid desiccant dehumidification](/preview/png/789800.png)
This paper reports a performance analysis for a hybrid air conditioning system. In this system, the sensible heat load is primarily treated by a vapor compression heat hump; the latent heat load is treated by a liquid dehumidification system that uses a lithium chloride solution as a desiccant. In addition, by decreasing the humidity ratio of air flowing through the outdoor heat exchanger of the vapor compression heat pump, frosting can be retarded. The overall system performance was evaluated by a cycle simulation conducted both in summer and winter modes. Compared to a traditional air conditioning system, the hybrid air conditioning system improves the coefficient of performance (COP) by approximately 20% and 100% in summer and winter, respectively.
Journal: International Journal of Refrigeration - Volume 33, Issue 1, January 2010, Pages 116–124