کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
789972 | 1466476 | 2008 | 12 صفحه PDF | دانلود رایگان |

General models for the design of the heat exchangers (absorber, generator, condenser and evaporator) of a prototype of an air-cooled absorption chiller of 2 kW for air-conditioning using the pair H2O–LiBr have been developed. An absorption machine of such characteristics has been constructed to be used as a test facility for validating the results obtained from the mathematical models developed. The discrepancies considering the heat exchanged between numerical results and experimental data are under 15% in most cases for all these components except the condenser, where the discrepancies are higher. The conclusions reported will lead to: (i) future improvements of the mathematical simulation models and (ii) improvements in the experimental infrastructure.
Journal: International Journal of Refrigeration - Volume 31, Issue 1, January 2008, Pages 75–86