کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
790074 | 1466404 | 2016 | 18 صفحه PDF | دانلود رایگان |

• The performance and efficiency of the CMCTR model are studied experimentally.
• The model has superior performance compared to the conventional compressor.
• The results satisfy a maximum 3% error for all air-condi. operational conditions.
• The cooling capacity and consumption power are compared for power and saving mode.
The capacity and efficiency of a capacity modulation compressor based on a two-stage rotary compressor are studied experimentally. The test results are compared with results from a numerical analysis (Part Ι). The proposed compressor has superior performance and efficiency compared to the conventional bypass-type single-stage compressor. The results satisfy a maximum 3% error requirement for all air conditioning operational conditions. Our results show that for the power mode, the cooling capacity (1% higher than that of the bypass-type) and power consumption (3% lower than that of the bypass-type) of the two-stage rotary compressor are slightly improved. For the saving mode, the cooling capacity (10% higher than that of the bypass-type) and power consumption (8% lower than the bypass-type) are significantly improved. In addition, the results of a loss analysis based on the pressure–volume (P–V) diagram exactly matched the results of the numerical simulation.
Journal: International Journal of Refrigeration - Volume 61, January 2016, Pages 82–99