کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
792873 1466475 2008 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Frost retardation of an air-source heat pump by the hot gas bypass method
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Frost retardation of an air-source heat pump by the hot gas bypass method
چکیده انگلیسی

This study is concerned with a hot gas (refrigerant) bypass method to retard the formation and propagation of frost in an air-source heat pump. The feasibility of the hot gas bypass method was investigated experimentally and the method's performance is compared with that of a normal, 1.12 kW capacity air-source heat pump system with no defrost equipment such as an electric resistance heater. Results indicate that the hot gas bypass method is useful for retarding the formation and growth of frost at the outdoor coil. The best performance is shown under a bypass refrigerant flow rate of 0.2 kg/min (20% of the whole system refrigerant flow rate). During 210 min of heat pump operation, the hot gas bypass method improved COP and heating capacity at an average of 8.5% and 5.7%, respectively, relative to the normal system.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 31, Issue 2, March 2008, Pages 328–334
نویسندگان
, , ,