کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
792941 1466477 2007 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Mass flow characteristics and empirical modeling of R22 and R410A flowing through electronic expansion valves
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Mass flow characteristics and empirical modeling of R22 and R410A flowing through electronic expansion valves
چکیده انگلیسی

The applications of electronic expansion valves (EEVs) into multi-type heat pumps and inverter heat pumps in building air-conditioning systems have increased for comfort environmental control and energy conservation. However, test data and mass flow models of EEVs are very limited in open literature. The objectives of this study are to investigate the mass flow characteristics of R22 and R410A through EEVs and to develop an empirical correlation for the prediction of mass flow rates of R22 and R410A through EEVs. Mass flow rates through six EEVs were measured by varying the EEV opening, inlet and outlet pressures, and the subcooling. Mass flow rates of R410A were compared with those of R22 at the same test conditions. Based on the experimental data, an empirical correlation for mass flow predictions in EEVs was developed by modifying the orifice equation. The predictions of the present correlation showed good agreement with the measured data with average and standard deviations of 0.76% and 5.9%, respectively. Approximately 92% of the measured data were within ±10% of the predictions.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 30, Issue 8, December 2007, Pages 1401–1407
نویسندگان
, , , ,