کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
793003 1466491 2006 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
The application of photo-coupler for frost detecting in an air-source heat pump
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
The application of photo-coupler for frost detecting in an air-source heat pump
چکیده انگلیسی

This experimental study is carried out to investigate reliability and effectiveness of a new method of using photo-coupler for detecting frost formation in an air source heat pump, and further to determine the most efficient initiation point of the defrost cycle. This new method of using photo-coupler as a frost sensing device is evaluated by comparing its performance with conventional time control defrost system in which defrost cycle is set to start at predetermined interval, e.g. about at every 1–1.5 h. Results indicate that overall heating capacity of photo-coupler detection method (case IV) is 5.5% higher than that of time control method. It is also shown that for maximum efficiency the defrost cycle must be initiated before the frost build-up area exceeds 45% of total front surface of the outdoor coil.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 29, Issue 2, March 2006, Pages 191–198