Fire tests to study heat insulation scenario of galvanized rolling shutters sprayed with intumescent coatings
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی (عمومی)
پیش نمایش صفحه اول مقاله
Fire tests to study heat insulation scenario of galvanized rolling shutters sprayed with intumescent coatings
چکیده انگلیسی

The purpose of this study, through standard furnace fire tests and a natural fire test, is to analyze the heat insulation behavior of galvanized rolling shutters sprayed with intumescent coatings. The following experiments and associated estimations demonstrated that in the 1-h standard fire-resisting tests, the radiant heat flux at a measuring point horizontally 1 m away from the center of an unexposed surface the radiation could reach 4.64 W/cm2 for the traditional uninsulated galvanized rolling shutter, and that the radiant heat flux would be substantially decreased to 0.22 W/cm2 for one with intumescent coating of 0.3 mm target thickness, which, during the heating process, expanded about 100 times in volume and then generated a certain insulation effect. Therefore the intumescent coatings on galvanized rolling shutters have been proved by this study to be a feasible method of insulation, which can be applied in the future fire compartment design of buildings.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Materials & Design - Volume 30, Issue 7, August 2009, Pages 2576–2583