کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
9637553 502012 2005 13 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Moderately high temperature water source heat-pumps using a near-azeotropic refrigerant mixture
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Moderately high temperature water source heat-pumps using a near-azeotropic refrigerant mixture
چکیده انگلیسی
A ternary mixture of R124/R142b/R600a, named HTR01, for moderately high temperature heat pumps, was developed. Tests of material compatibility and oil miscibility showed that the mixture could be used with a R22 compressor in an HTR01 heat-pump system. A 2.92 kW moderately high temperature water source heat pump system was set up with HTR01 as the refrigerant to study the system performance with HTR01. Then, a 300 kW moderately high temperature water source heat pump system was built with HTR01 as the refrigerant to test the performance with a geothermal hot water source. The test showed that the condenser outlet water temperature could reach and hold on about 90 °C with a high coefficient of performance.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 80, Issue 4, April 2005, Pages 435-447