کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
9708149 1466494 2005 11 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental investigation of oil retention in air conditioning systems
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Experimental investigation of oil retention in air conditioning systems
چکیده انگلیسی
In air conditioning and refrigeration systems a small amount of oil is carried with the refrigerant and is retained in the system components. Oil retention characteristics in the condenser, evaporator, liquid and suction lines were measured and are presented and discussed here. Refrigerants R22, R410A, and R134a with miscible and non-miscible lubricants were considered to investigate oil retention physics in the widest possible range of transport properties. A parametric analysis in the suction line showed that oil retention depends on the oil mass fraction, vapor refrigerant mass flux, mixture viscosity ratio and orientation of the pipe. In the suction line, an increase in mixture viscosity of about 55% caused a rise in oil retention in the range of 50%, depending on the oil mass fraction. Oil retention in the upward vertical suction line is about 50% higher than in the horizontal line at similar conditions.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 28, Issue 7, November 2005, Pages 1018-1028