کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
10283165 502676 2005 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
A feasibility study of a ventilated beam system in the hot and humid climate: a case-study approach
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
A feasibility study of a ventilated beam system in the hot and humid climate: a case-study approach
چکیده انگلیسی
The applications of ventilated beam systems in the hot and humid climate are limited. The main reason is the high risk of condensation. A case-study measurement was conducted in a typical office building in Singapore to investigate the feasibility of a ventilated beam system in the Tropics. The results show that the condensation in the beam system is possible to prevent and to reach dry cooling if infiltration is minimized, supply airflow rate is sufficient to extract humidity of people and tuning of the automation system has conducted probably.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Building and Environment - Volume 40, Issue 9, September 2005, Pages 1164-1173