کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
10286079 504142 2005 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Investigation of indoor climate and power usage in a data center
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Investigation of indoor climate and power usage in a data center
چکیده انگلیسی
The power requirement within the data center is considerably high, due to an oversized air conditioning system. An infrared camera was used to visualize the airflow and temperature pattern, showing that cool air does not reach the upper levels of the racks, despite a very high air exchange rate. Point measurements of temperatures in a rack show that recirculation cells are present, causing accumulation of heat and improper cooling of electronic equipments. Thus, the chilled air is not distributed properly and consequently the cooling energy is not used effectively.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 37, Issue 10, October 2005, Pages 1075-1083
نویسندگان
, ,