کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
243932 501939 2012 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Performance analysis of an integrated UFAD and radiant hydronic slab system
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Performance analysis of an integrated UFAD and radiant hydronic slab system
چکیده انگلیسی

In this paper, an EnergyPlus model was used to simulate the operation of a novel integrated HVAC system. This system combines an underfloor air distribution system with a cooled radiant ceiling slab. A cooling tower supplies water to pre-cool the structural slabs during the night and early morning period. The paper compares the performance of this system to both a typical overhead system and a typical UFAD system in the cooling season for the Sacramento, California climate. When compared to the overhead system, the integrated UFAD/Radiant system shows a 22–23% reduction in total energy consumption during the peak cooling months (June to August) and a 31% reduction in peak hourly electricity demand. When compared to the UFAD system, these reductions are 21–22% and 24% respectively. An investigation of the simulation results showed that the integrated UFAD/Radiant system also improves occupant thermal comfort and reduces thermal decay issues in the underfloor plenum.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 90, Issue 1, February 2012, Pages 250–257
نویسندگان
, , , ,