کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
244281 501945 2011 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental diagnosis of the influence of operational variables on the performance of a solar absorption cooling system
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Experimental diagnosis of the influence of operational variables on the performance of a solar absorption cooling system
چکیده انگلیسی

This paper presents the analysis of the performance of a solar cooling facility along one summer season using a commercial single-effect water–lithium bromide absorption chiller aiming at domestic applications. The facility works only with solar energy using flat plate collectors and it is located at Universidad Carlos III de Madrid, Spain. The statistical analysis performed with the gathered data shows the influence of five daily operational variables on the system performance. These variables are solar energy received along the day (H  ) and the average values, along the operating period of the solar cooling facility (from sunrise to the end of the cold-water production), of the ambient temperature (T¯), the wind velocity magnitude (V), the wind direction (θ) and the relative humidity (RH). First order correlation functions are given. The analysis of the data allows concluding that the most influential variables on the daily cooling energy produced and the daily averaged solar COP are H, V and θ. The period length of cold-water production is determined mainly by H   and T¯.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 88, Issue 4, April 2011, Pages 1447–1454
نویسندگان
, , , , , ,