کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
249730 502626 2008 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
HVAC air-quality model and its use to test a PM2.5 control strategy
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
HVAC air-quality model and its use to test a PM2.5 control strategy
چکیده انگلیسی

This paper presents a MATLAB® Simulink air-quality model of a commercial building with a heating, ventilation, and air conditioning (HVAC) system in Fairbanks, Alaska. Outdoor and indoor real-time fine particulate matter (PM2.5) levels were measured at this building during a summer wild-fire smoke episode and then during a winter period. The correlation coefficient between the model-predicted and the measured indoor concentrations was 0.99 for the summer and 0.98 for the winter, justifying the usability of the model for further studies. An HVAC control algorithm was developed that reduces the indoor PM2.5 levels. The algorithm was tested using the HVAC Simulink model and the outdoor PM2.5 data from the summer smoke episode. The average indoor PM2.5 level with this control algorithm was 65% lower than with the regular control. Thanks to the PM2.5 control strategy being automatically engaged only during episodes, it was shown to have the potential of significantly reducing the indoor PM2.5 levels without significantly compromising the purpose of the original control strategy.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Building and Environment - Volume 43, Issue 11, November 2008, Pages 1850–1857
نویسندگان
, ,