کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
249980 | 502646 | 2007 | 10 صفحه PDF | دانلود رایگان |
The main thrust of this research was to develop a simplified cooling capacity estimation model for a suspended (free-hanging type) metal ceiling radiant cooling panel. By statistically analyzing panel performance data generated by a validated analytical panel model, the impact of various design parameters and their combinations on the panel cooling capacity was estimated. And then a linear regression equation was derived as a function of major design parameters and interactions which have significant effects on the panel capacity. In this analysis, eight single parameters and 13 two-factor interactions showed significant impact on the panel cooling capacity. Consequently, a simplified regression model for a free hanging panel was derived as a function of those selected parameters. The proposed model could estimate the panel cooling capacity not only for the natural convection but also for the mixed convection condition present in a mechanically ventilated space.
Journal: Building and Environment - Volume 42, Issue 9, September 2007, Pages 3176–3185