کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
250035 | 502650 | 2007 | 9 صفحه PDF | دانلود رایگان |
![عکس صفحه اول مقاله: Scale model study of airflow performance in a ceiling slot-ventilated enclosure: Non-isothermal condition Scale model study of airflow performance in a ceiling slot-ventilated enclosure: Non-isothermal condition](/preview/png/250035.png)
Scale-model study of a non-isothermal ceiling slot-ventilated enclosure was investigated in both airspeed and thermal fields. Results of airflow pattern, centerline velocity and centerline temperature decay, velocity and temperature profile, airflow boundary layer and thermal boundary layer growth, floor velocity, and floor temperature difference were analyzed to establish semi-empirical prediction equations. Results also compared with previous researches to validate the physical behavior of air-jet. Data of centerline velocity decay showed similar airflow characteristics as isothermal air-jet with Archimedes number (Ar)<0.004(Ar)<0.004, which performed as pseudo-isothermal airflow. Air-jet fell on entry with Ar>0.018Ar>0.018. A single circulation airflow existed at 0.004
Journal: Building and Environment - Volume 42, Issue 3, March 2007, Pages 1142–1150