Improvement of solar-electric compression refrigeration system through ejector-assisted vapour compression chiller for space conditioning in subtropical climate
چکیده انگلیسی

In this study, improvement was made for the solar-electric compression refrigeration system by incorporating the ejector design to a conventional vapour compression chiller within the system. Through year-round dynamic simulation, the performances of the ejector-assisted vapour compression chiller (EAVCC) were evaluated under the intermittent and changing supply of solar energy in the subtropical climate. In addition, the effect of three common refrigerants, R22, R134a and R410A on the EAVCC was assessed and compared. It was found that the coefficient of performance of the chiller was increased and the total primary energy consumption of the system was decreased for all the three refrigerants, in which the degree of enhancement from R134a was the most significant. It was also noted that the effect of R410A on EAVCC was not apparent, and the overall system energy improvement was marginal. With appropriate ejector design and refrigerant selection of the solar-electric compression refrigeration system, the reduction potential of year-round primary energy consumption could be more than 5%. This would be certainly helpful in promoting the application of solar air-conditioning for building use in the subtropical climate.


► Improvement was made for solar-electric compression refrigeration by incorporating ejector design.
► The effect of R22, R134a and R410A on EAVCC was assessed and compared.
► COP of EAVCC was increased and system primary energy consumption decreased.
► The degree of enhancement from R134a was the best, while that from R410A was not apparent.
► The annual primary energy saving could be more than 5%.