Computer modeling of displacement ventilation systems based on plume rise in stratified environment
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
Computer modeling of displacement ventilation systems based on plume rise in stratified environment
چکیده انگلیسی

A model for displacement ventilation system based on plume rise of single point heat source was developed. The errors for temperature gradient ratio were less than 6% in most cases. Errors for temperature gradient and displacement zone height were relatively higher (up to 28.1%) which might be due to the derivation of the parameters from experimental data. Still, the errors were lower than those from design model/method of some other workers (68.5% for the temperature gradient ratio and 15.7% for the temperature difference between the supply air and at 0.1 m above floor level). With a room height of 2.4 m (common for office in Hong Kong) and design room temperature 25.5 °C defined at 1.1 m above floor level under the normal load to air flow ratio of 12,000 W/m3/s (typical values for sub-tropical region) and minimum supply temperature of 18 °C, there existed a zone capacity range from 1000 to 5000 W that stand alone operation displacement ventilation system was feasible and that the displacement zone height (minimum 2.2 m) was above normal breathing level. The feasible zone capacity range diminished with decrease in design room temperature and/or room height. In this case, the load to air flow ratio had to be reduced, resulting in a higher flow rate when compared to a mixing ventilation system, or an auxiliary cooling facility such as a chilled ceiling had to be used.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 39, Issue 4, April 2007, Pages 427–436
نویسندگان
, ,