												An analysis carried out on the High Voltage A (HVA) electricity power distribution network run by Cameroon’s AES-SONEL company shows that losses are very high due to energy which is produced but not distributed and that the duration of power interruptions as a result of the defects is long due to the time used in searching for these defects, particularly in rural zone’s supply. Given that quick detection of defects is a sure means of improving availability and productivity in any company, we hereby propose a system of real-time diagnosis of the defects on a rural network’s supply of AES-SONEL’s electric power distribution network, the case of. After an inventory of typical defects on electric power networks and the proposal of a tool for their identification, we propose a system for the detection and localization of these various failures. The implementation of the system on a Programmable Logic Controller (PLC) enables the performance of the system to be assessed.
►  Manual management has high rate of interruption in the AES-SONEL network. 
►  Loos-of-phase in the network is signalled by consumers. 
►  Circuit breaker D31 tripped 54 times; this led to 398 h of power cuts. 
►  A system for the detection and localization of the various defects is proposed. 
►  An algorithm of real-time monitoring of Monatélé’s supply network is proposed.
Journal: International Journal of Electrical Power & Energy Systems - Volume 45, Issue 1, February 2013, Pages 229–234