کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
398949 1438755 2013 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Lightning back flashover double circuit tripping pattern of 132 kV lines in Malaysia
موضوعات مرتبط
مهندسی و علوم پایه مهندسی کامپیوتر هوش مصنوعی
پیش نمایش صفحه اول مقاله
Lightning back flashover double circuit tripping pattern of 132 kV lines in Malaysia
چکیده انگلیسی

This paper presents a study on flashover patterns due to double tripping using EMTP software. The simulation was performed on a 132 kV line double circuit for economic installation of transmission line arresters (TLAs). The simulation results were validated with the field data of 132 kV transmission line in Malaysia. A vertically configured double circuit transmission line was modelled and the effects of tower footing resistance, lighting current values, power frequency voltage and the coupling effect of the phase conductors study were taken into account. A good agreement between the simulation and field data was obtained. A specific back flashover phase of the double circuit line can be determined by considering the effects that have been mentioned. Through determination of the tripping pattern, a suitable installation of line arresters and mitigation of line tripping due to back flashover can be achieved.


► Simulation using EMTP for lightning-caused flashover pattern of 132 kV double circuit.
► 70% of line outages are due to lightning and significant number is double circuit tripping.
► Determination of parameters that influence flashover pattern was verified using EMTP.
► Parameters are frequency voltage, coupling factor, lightning current and footing resistance.
► Based on the tripping pattern line lightning arrester can be economically installed.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Electrical Power & Energy Systems - Volume 45, Issue 1, February 2013, Pages 235–241
نویسندگان
, , , ,