Fault location using synchronized sequence measurements
موضوعات مرتبط
مهندسی و علوم پایه مهندسی کامپیوتر هوش مصنوعی
پیش نمایش صفحه اول مقاله
Fault location using synchronized sequence measurements
چکیده انگلیسی

This paper proposes fault location formulas using synchronized sequence measurements. For earth faults, zero-sequence voltages and currents at two terminals of faulted line are applied to fault location. Negative-sequence measurements are utilized for asymmetrical faults and positive-sequence measurements are used for three-phase faults. The fault location formulas are derived from a fault location technique [Wang C, Dou C, Li X, Jia Q. A WAMS/PMU-based fault location technique. Elect Power Syst Res 2007;77(8):936–945.] based on WAMS/PMU. The technique uses synchronized fault voltages measured by PMUs in power network. The formulas are simple and are easy for application. Case studies on a testing network with 500 kV transmission lines including ATP/EMTP simulations are presented. Various fault types and fault resistances are also considered.