• Primary and secondary frequency response is extracted over active power generation.
• Primary and secondary frequency response are examined in time and frequency domain.
• The performance of proposed algorithm is tested on both synthetic and real data.
Frequency control is a vital component of a secure and robust power grid and it ought to be closely monitored. Frequency control consists of two main components; primary and secondary control and their contributions are usually aggregated in the active power generation data of a plant, which is acquired via Supervisory Control And Data Acquisition. In many cases, such as in Turkey, they are demanded to be evaluated separately due to different impacts on power system or different financial policies. However, this is not usually a straightforward process since primary and secondary response cannot be obtained distinctly.In this work, Extraction of Primary and Secondary Control (EPSCon) algorithm is introduced to extract primary and secondary response over active power generation data. Based on time and frequency domain characteristics of primary and secondary response, EPSCon is developed on a Expectation-Maximization type recursive scheme employing Generalized Cross Correlation and ℓ1ℓ1 Trend Filtering techniques. Favorably, EPSCon uses a simple plant model built upon basic governor and plant load controller technical characteristics as an initial estimate of primary and secondary response.
Journal: International Journal of Electrical Power & Energy Systems - Volume 73, December 2015, Pages 16–22