A novel protection for powerformers in NIEPS
چکیده انگلیسی

A new type of high-voltage generator which offers a direct connection to the power network without the need for a step-up transformer is called powerformer. The neutral of the most powerformers is unearthed which belongs to NIEPS. When a stator single phase-to-ground fault occurs in a powerformer, every generator that is connected in parallel with the faulty powerformer has the same voltage. Traditional protection schemes using zero sequence voltage and third-harmonic voltage signals cannot detect which powerformer is faulted. In order to solve this problem for powerformer protection, a novel stator single phase-to-ground fault protection based on the direction and magnitude of zero-sequence currents is proposed in this paper. Simulation results have shown that, under different fault conditions, the new scheme can distinguish reliably internal faults from external faults, and can detect stator single phase-to-ground fault occurred in which powerformer with resistance 1 kΩ. A 100% of the winding can be fully protected.


► The stator single phase-to-ground fault protection for powerformers.
► Comparing the direction of zero-sequence current of each powerformer.
► Comparing the magnitude of zero-sequence current of each powerformer.
► Powerformers can be detected in 100% of the winding with resistance 1 kΩ.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Electrical Power & Energy Systems - Volume 34, Issue 1, January 2012, Pages 75–80
نویسندگان
, , , , ,